Optional Cooling Configurations
Technical Specifications
In addition to the Standard Units, Silver Linings Rafts can be designed and constructed to meet individual customer requirements. Tell us about your needs.
|
SIlver Linings Raft (1000 Series) Specifications INDIVIDUAL STANDARD UNITS |
||||
|
Model |
1R-4 |
1R-5 |
2R-4 |
2R-5 |
|
Service Class |
Preventative Maintenance (PM) |
Run-to-Failure (RTF) |
||
|
Size |
86"W x 103"L x 100"H |
|||
|
Rows of IT Racks |
1 |
1 |
2 |
2 |
|
IT Racks / Row |
4 |
5 |
4 |
5 |
|
IT Rack Style |
45U, Cabinet, Open Face |
45U, 4-Post, Open Face |
45U, 4-Post, Open Face |
45U, 4-Post, Open Face |
|
RMU Capacity |
180 |
225 |
360 |
450 |
|
1 IT Equipment Weight (lbs) |
5,060 |
6,325 |
10,120 |
12,650 |
|
Rack Weight (lbs) |
400 |
500 |
800 |
1,000 |
|
2 Silver Linings Raft-IT Wt (lbs) |
3,500 |
3,500 |
3,500 |
3,500 |
|
Total (lbs) |
8,960 |
10,325 |
14,420 |
17,150 |
|
Total Weight / ft2 |
146 |
168 |
234 |
279 |
|
150 |
150 |
80 |
80 |
|
|
5 Cooling Tons Required |
42.7 |
42.7 |
22.7 |
22.7 |
|
140 |
140 |
70 |
70 |
|
|
IT Equipment Power/Rack (kW/Rack) |
35 |
28 |
9 |
7 |
|
IT Equipment Power (Watts/ft2) |
2,276 |
2,276 |
1,138 |
1,138 |
|
6 PUE |
1.07 |
1.07 |
1.14 |
1.14 |
|
STANDARD SILVER LININGS RAFTS IN HI-CUBE ISO CONTAINERS |
||||||||||||
|
Silver Linings Raft |
1R-4 |
1R-5 |
2R-4 |
2R-5 |
1R-4 |
1R-5 |
2R-4 |
2R-5 |
1R-4 |
1R-5 |
2R-4 |
2R-5 |
|
Container Length (ft) |
20 |
40 |
53 |
|||||||||
|
IT Equipment Rafts / Container |
2 |
4 |
5 |
|||||||||
|
Utility Rafts / Container |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
|
Service Class |
PM |
PM |
RTF |
RTF |
PM |
PM |
RTF |
RTF |
PM |
PM |
RTF |
RTF |
|
RMU Capacity |
360 |
450 |
720 |
900 |
720 |
900 |
1,440 |
1,800 |
900 |
1,125 |
1,800 |
2,250 |
|
IT Rows |
2 |
2 |
4 |
4 |
4 |
4 |
8 |
8 |
5 |
5 |
10 |
10 |
|
IT Equipment Wt (lbs) |
10,120 |
12,650 |
20,240 |
25,300 |
20,240 |
25,300 |
40,480 |
50,600 |
25,300 |
31,625 |
50,600 |
63,250 |
|
Utility Wt (lbs) |
200 – 400 |
200 – 400 |
200 – 400 |
|||||||||
|
Container Wt (lbs) |
6,000 |
11,900 |
15,800 |
|||||||||
|
7 Total Wt (lbs) - Fully Equipped |
25,870 |
28,600 |
36,790 |
42,250 |
49,690 |
55,150 |
71,530 |
82,450 |
62,550 |
69,375 |
89,850 |
103,500 |
|
300 |
160 |
600 |
320 |
750 |
400 |
|||||||
|
280 |
140 |
560 |
280 |
700 |
350 |
|||||||
|
IT Equipment Power / ft2 (Watts / ft2) |
1,750 |
875 |
1,750 |
875 |
1,651 |
825 |
||||||
|
6 PUE |
1.07 |
1.14 |
1.07 |
1.14 |
1.07 |
1.14 |
||||||
2. Module weight includes all components, minus IT racks and IT equipment
3. Assumes a 1:1 ratio (electrical power load: cooling load)
4. Assumes a 65°F chilled water source and a max allowable cold aisle temperature of 95°F Lower temperature water produces much greater cooling performance.
5. Assumes the use of a refrigeration cycle to provide source water at 65°F
6. Assumes only the parasitic losses associated with on-board fan motors
7. Includes fire suppression, electrical termination, hydraulic termination equipment and controls
Silver Linings Features
A. Interior Track Lighting (optional) B. Equipment Power Access, to customer specification C. Coolant Tubes beneath flooring isolate equipment from fluids and enhance operator safety. D. Multi-unit Fan Panel and E overhead, powered Cooling Ducts create "Augmented Convective Cooling" across full face of equipment racks. F. Heat Exchanger Core produces patented airflow pattern that cools better than conventional coil systems. G. Equipment Racks — contents determined by customer specification H. Moveable Equipment Base provides access to either side of racks, and maximizes rack size. I. Steel Flooring Joists and Fork Pockets provide quick, easy and safer movement of modules. Available in Standard-size Modules — for ISO container housings — or custom configurations.